Conductor: Rigid polished copper class I s /. UNE-EN 60228
Insulation: EN 50363-1 - Silicone cross-linked rubber (SiR) type EI-2.
Identifications: For > 5 conductors, Numbered Black + Yellow/Green, HD 308 S2 (Up to 5 Conductors)
Assembly: Concentrically wired insulated conductors.
Outer cover: UNE-EN 50363-8 - Halogen-free TM-7 thermoplastic roofing compounds.
Color: ORANGE
Operating voltage: 300/500V
Test voltage: 2.500V 5min
Operating temperature: -15...+90ºC (250ºC / 5 segundos en cortocircuito)
Standards:
(Construction) NF C 32-310 - Fire-resistant cables.
(Insulation) EN 50363-1 - Silicone cross-linked rubber (SiR) type EI-2.
(Sheath) UNE-EN 50363-8 - Halogen-free TM-7 thermoplastic roofing compounds.
(Fire) Cat. C1 according to NF C 32-070 - Fire retardant.
(Fire) UNE-EN 60754-2 (IEC 60754-2) - Low corrosiveness of fumes.
(Fire) UNE-EN 61034 (IEC 61034) - Low smoke emission.
(Fire) UNE-EN 60332-1 (IEC 60332-1) - Flame-retardant.
(Fire) Cat. CR1 según NF C 32-070 - Fire resistant.
(Fire) UNE-EN 60754-1 (IEC 60754-1) - Halogen-free.
Fill in the following fields to request the cable technical sheet in PDF format and the Declaration of Performance (DOP)