JE-H(St)H...Bd FE180/PH90/E30

FIRE & ALARM  |  FIRE RESISTANT CABLES

JE-H(St)H...Bd FE180/PH90/E30

Construction

Conductor: Rigid polished copper class I s /. UNE-EN 60228
Insulation: EN 50363-1 - Silicone cross-linked rubber (SiR) type EI-2.
Identifications: Colours according to VDE 0815.
Assembly: Pairs
Protector: Polyester ribbon.
Protector 2: Fibreglass tape.
Pantalla general Al/Pet: Aluminium/Polyester Tape.
Drenaje general: Rigid tinned copper wire.
Outer cover: UNE-EN 50363-8 - Halogen-free TM-7 thermoplastic roofing compounds.
Color: ORANGE

JE-H(St)H...Bd FE180/PH90/E30
CE CE
Flame retardant Flame retardant
Fire retardant Fire retardant
Low gas corrosiveness Low gas corrosiveness
Low smoke opacity Low smoke opacity
Solid Wire Solid Wire
Halogen free Halogen free
CPR Compilant CPR Compilant
RoHS RoHS
Fire resistant Fire resistant

Technical data / Regulations.

Operating voltage: 300/500V
Test voltage: 2.500V 5min
Operating temperature: -15... +90ºC
Standards:
(Construction) Based DIN VDE-0815 - Shielded telephone cables for indoor installations.
(Insulation) EN 50363-1 - Silicone cross-linked rubber (SiR) type EI-2.
(Sheath) UNE-EN 50363-8 - Halogen-free TM-7 thermoplastic roofing compounds.
(Fire) UNE-EN 61034 (IEC 61034) - Low smoke emission.
(Fire) UNE-EN 60332-1 (IEC 60332-1) - Flame-retardant.
(Fire) UNE-EN 60332-3 (IEC 60332-3) Cat C - Fire retardant.
(Fire) UNE-EN 60754-1 (IEC 60754-1) - Halogen-free.
(Fire) EN 50200, IEC 60331-2 (para Ø < 20mm) - Intrinsic resistance: PH90 (90 minutes at 840°C).
(Fire) IEC 60331 / DIN VDE 0472-814 - Intrinsic resistance 180 minutes FE-180.
(Fire) UNE-EN 50575 - CPR
(Fire) UNE-EN 60754-2 (IEC 60754-2) - Low corrosiveness of fumes.
(Test) DIN VDE 4102 part 12 - Circuit integrity E30.
(Directives) 2011/65/EU - RoHS Directive.
(Directives) 2014/35/EU - Low Voltage Directive.

Info request

Fill in the following fields to request the cable technical sheet in PDF format and the Declaration of Performance (DOP)

If you have any inquire, we are here to help.