Conductor: Flexible polished copper rope class V s/. UNE-EN 60228.
Insulation: UNE-EN 21123-4 - Mica + XLPE type DIX3 according to HD603-1.
Identification: HD 308 S2
Assembly: Concentrically wired insulated conductors.
Outer cover: UNE-EN 21123-4 - Polyolefin LSZH.
Color: Orange or Black
CPR classification: Eca
Operating voltage: 0,6/1KV
Test voltage: 3.500 V C.A. 5 min.
Standards:
(Construction) UNE-EN 21123-4 (IEC 60502) - Power cables for industrial use 0.6/1kV.
Cross-linked polyethylene insulation (XLPE) and polyolefin sheath.
(Insulation) EN 50363-1 - Cables with intrinsic resistance to fire for use in safety circuits.
(Fire) UNE-EN 50575 - CPR
(Fire) UNE-EN 60754-2 (IEC 60754-2) - Low corrosivity of smoke.
(Fire) UNE-EN 61034 (IEC 61034) - Low smoke emission.
(Fire) UNE-EN 60332-1 (IEC 60332-1) - Flame-retardant.
(Fire) UNE-EN 60332-3 (IEC 60332-3) Cat C - Fire retardant.
(Fire) UNE-EN 60754-1 (IEC 60754-1) - Halogen-free.
(Fire) EN 50200, IEC 60331-2 (for Ø < 20mm) - Intrinsic resistance: PH120 (120 minutes at 840°C).
(Fire) EN 50362, IEC 60331-1 (for Ø > 20mm) - Intrinsic resistance: PH120 (120 minutes at 840 °C).
Flexible cable for the transport and distribution of electrical energy in fixed installations, protected or not. Cables with intrinsic resistance to fire to maintain service during a fire in security circuits, for example: signaling, detection and alarm circuits, circuits for evacuation and fire fighting services, etc. Especially suitable for installations in public places where a safe behavior of the cable is required in the event of fire, with low smoke opacity and minimizing the harmful effects of corrosive gas inhalation.
Fill in the following fields to request the cable technical sheet in PDF format and the Declaration of Performance (DOP)